Voltage: 12/24VDC
Current: 10
The GCU-10 has five pins dip switch that set thespecification of the genset.
SW1 - Generator Frequency
ON - 50Hz OFF - 60Hz
SW2 - Battery Voltage
ON - 12V OFF - 24V
SW3 - Stop Solenoid
ON - Energize to Start,OFF - Energize to Stop
SW4 - Oil Pressure Switch Type
ON - Normal Open NO, OFF - Normal Close NC
SW5 - Oil Pressure Switch
(Crank Disconnect)
ON - not used for crank disconnet
OFF - used for crank disconnet<
The module starts and stops the generator, and at the same time indicates the operation status and fault conditions,
If it senses a fault it will automatically shuts down the engine and indicates the engine failure by means of eight LEDs.
The technician can program the module according to different generator requirements complying with different conditions and protections.
Protection Setting
Engine fail to start reattempt:
Engine tries 3 times to start
Engine High Water temperature Protection:
Shutdown activated after 3 sec delay by N/O contacts
Engine Low Oil Pressure Protection:
Shutdown activated after 3 seconds,
Oil Pressure Switch switchable to N/O or N/C sender type.
Engine Over-speed Protection
Shutdown activated after 3 seconds,
50Hz is activated at 55 Hz, 60Hz is activated at 66 Hz
Engine Under Speed Protection:
Shutdown activated after 5 seconds,
50Hz is activated at 45 Hz, 60Hz is activated at 56 Hz
Emergency Shutdown:
Shutdown activated by NO. Contacts
Spare / User define Shutdown:
Shutdown activated after 5 sec delay by NO. Contacts
Low Battery Voltage Warning:
Activated after 5 seconds delay
12VDC activated at 10VDC, 24VDC activated at 20DCV
Adjustment
In the back, the GCU-10 has five adjustment pots that change the time delay functions.
NOTICE: High Voltage can be harmful/fatal! By purchasing this or any generator control panel, you agree to be responsible for the installation and application. The generator conrol panel should be installed by a qualified technician. Green Power South Pacific P/L will not be responsible for any incidental or consequential damages or personal injury. Our liability is limited to repair or replacement of the generator control panel if found defective.